TeSys GV motor circuit breaker, 3 poles (3P), 73A/690V, for 3-phase motor applications 37kW@400V. It provides a thermal-magnetic protection with a thermal setting range 62-73A, magnetic tripping at 15xIn, high breaking capacity Icu 50kA@400V. Connection by Everlink BTR screw terminals. Start-stop control by rotary knob guaranteed for 20 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
Specifications | |
Main | |
Range | TeSys Deca |
Product name | TeSys GV3 |
TeSys Deca | |
Product or Component Type | Motor circuit breaker |
Device short name | GV3P |
Device Application | Motor protection |
Trip unit technology | Thermal-magnetic |
Complementary | |
poles description | 3P |
network type | AC |
Utilisation category | AC-3 IEC 60947-4-1 |
Network frequency | 50/60 Hz |
Fixing mode | 35 mm symmetrical DIN rail clipped |
Panel screwed with 3 x M4 screws) | |
Motor power kW | 37 kW 400/415 V AC 50/60 Hz |
45 kW 500 V AC 50/60 Hz | |
55 kW 690 V AC 50/60 Hz | |
Breaking capacity | 65 kA Icu 230/240 V AC 50/60 Hz |
50 kA Icu 400/415 V AC 50/60 Hz | |
50 kA Icu 440 V AC 50/60 Hz | |
12 kA Icu 500 V AC 50/60 Hz | |
6 kA Icu 690 V AC 50/60 Hz | |
[Ics] rated service short-circuit breaking capacity | 100 % 230/240 V AC 50/60 Hz |
60 % 400/415 V AC 50/60 Hz | |
60 % 440 V AC 50/60 Hz | |
50 % 500 V AC 50/60 Hz | |
50 % 690 V AC 50/60 Hz | |
Control Type | Rotary handle |
Line Rated Current | 73 A |
Thermal protection adjustment range | 62…73 A IEC 60947-4-1 |
Magnetic tripping current | 1120 A |
[Ith] conventional free air thermal current | 73 A IEC 60947-4-1 |
[Ue] rated operational voltage | 690 V AC 50/60 Hz |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 6 kV IEC 60947-2 |
Phase failure sensitivity | Yes IEC 60947-4-1 |
Suitability for isolation | Yes IEC 60947-1 |
Power dissipation per pole | 8 W |
Mechanical durability | 50000 cycles |
Electrical durability | 20000 cycles AC-3 415 V In |
Rated duty | Continuous IEC 60947-4-1 |
Tightening torque | 44.3 lbf.in (5 N.m) screw clamp terminal |
Width | 2.2 in (55 mm) |
Height | 5.2 in (132 mm) |
Depth | 5.4 in (136 mm) |
Net Weight | 2.12 lb(US) (0.96 kg) |
color | Dark grey |
Environment | |
Product Certifications | CCC |
UL | |
CSA | |
EAC | |
ATEX | |
LROS (Lloyds register of shipping) | |
BV | |
ABS | |
DNV-GL | |
UKCA | |
IK degree of protection | IK09 enclosure |
IP degree of protection | IP20 IEC 60529 |
Climatic withstand | IACS E10 |
Ambient Air Temperature for Storage | -40…176 °F (-40…80 °C) |
Fire resistance | 1760 °F (960 °C) IEC 60695-2-11 |
Ambient air temperature for operation | -4…140 °F (-20…60 °C) |
Mechanical robustness | Shocks 5 Gn for 11 ms contactor open |
Shocks 30 Gn for 11 ms contactor closed | |
Vibrations 4 Gn, 5…300 Hz | |
Operating altitude | 9842.52 ft (3000 m) |
Ordering and shipping details | |
Category | US10I1122366 |
Discount Schedule | 0I11 |
GTIN | 3.60648E+12 |
Returnability | Yes |
Country of origin | FR |
Packing Units | |
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 2.677 in (6.800 cm) |
Package 1 Width | 5.827 in (14.800 cm) |
Package 1 Length | 6.299 in (16.000 cm) |
Package 1 Weight | 2.220 lb(US) (1.007 kg) |
Unit Type of Package 2 | S06 |
Number of Units in Package 2 | 120 |
Package 2 Height | 29.528 in (75.000 cm) |
Package 2 Width | 23.622 in (60.000 cm) |
Package 2 Length | 31.496 in (80.000 cm) |
Package 2 Weight | 287.659 lb(US) (130.480 kg) |
Contractual warranty | |
Warranty | 18 months |