The RCCBs F200 series assures protection to people and installations against fault current to earth. A large offer for standard instantaneous and selective AC and A types is completed with some configurations for special applications. Unpacked version.
MAIN SPECIFICATION | |
ABB Global ID | ABB2CSF202005R1400 |
Business Area (Master Data) Name | Electrification |
Catalog Description | F202 AC-40/0,03 IEC Residual Current Circuit Breaker |
Division (Master Data) Name | Smart Buildings |
EAN | 8012542814801 |
Rated Insulation Voltage (Ui) | 500 volt |
SKU ID | 2CSF202005R1400 |
TECHNICAL | |
Accessories Available | Yes |
Connecting Capacity | Busbar 10 mm² |
Rigid 25 … 25 mm² | |
Flexible 25 … 25 mm² | |
Electrical Endurance | 10000 cycle |
Maximum Surge Current | 0.25 kA |
Operating Characteristic | Instantaneous |
Options Provided | None |
Pollution Degree | 2 |
Power Loss | at Rated Operating Conditions per Pole 2.4 W |
Power Supply Connection | Arbitrary |
Product Name | Residual Current Circuit Breaker |
Rated Cross-Section | 4 – Multi-Wired 0…25 mm² |
1 – Solid-Core 25…25 mm² | |
Rated Frequency (f) | 50 / 60 Hz |
Standards | IEC 61008 |
TECHNICAL UL/CSA | |
Maximum Operating Voltage UL/CSA | 277 V AC |
Short-Circuit Current Rating (SCCR) | 0.03 A |
DIMENSIONS | |
Built-In Depth (t2) | 69 mm |
ORDERING | |
Minimum Order Quantity | 1 piece |
Selling Unit Of Measure | piece |
ENVIRONMENTAL | |
Ambient Temperature | -25…55 °C |
RoHS Status | Following EU Directive 2011/65/EU |
CLASSIFICATIONS | |
CN8 | 85363030 |
ETIM 6 | EC000003 – Residual current circuit breaker (RCCB) |
ETIM 7 | EC000003 – Residual current circuit breaker (RCCB) |
ETIM 8 | EC000003 – Residual current circuit breaker (RCCB) |
Object Classification Code | F |
WEEE B2C / B2B | Business To Consumer |
OTHER | |
Ambient Air Temperature | Operation -25…55 °C |
Degree Of Protection | IP2X |
Leakage Current Type | AC |
Mounting Type | DIN rail |
Number Of Poles | 2 |
Product Net Width | 0.035 |
Rated Conditional Short-Circuit Current (Inc) | 10 kA |
Rated Current (In) | 40 A |
Rated Impulse Withstand Voltage (Uimp) | 4 kilovolt |
Rated Operational Voltage | 230 V |
Rated Residual Current | 30 mA |
Rated Service Short-Circuit Breaking Capacity (Ics) | 1 kA |
Rated Voltage (Ur) | 230 V |
Type Of Residual Current | AC type |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
Width In Number Of Modular Spacings | 2 |