Specifications | |
Main | |
Range | PowerLogic |
Product name | PowerLogic PM5000 |
Device short name | PM5310 |
Product or component type | Power meter |
Complementary | |
Power quality analysis | up to the 31st harmonic |
Device application | Multi-tariff |
Power monitoring | |
Type of measurement | Current |
Voltage | |
Frequency | |
Power factor | |
Energy | |
Active and reactive power | |
supply voltage | 90…450 V AC 45…65 Hz |
100…300 V DC | |
Network frequency | 50 Hz |
60 Hz | |
[In] rated current | 1:00 AM |
5:00 AM | |
type of network | 1P + N |
3P | |
3P + N | |
Maximum power consumption in VA | 11 VA at 415 V |
Ride-through time | 80 ms 120 V AC typical |
100 ms 230 V AC typical | |
100 ms 415 V AC typical | |
50 ms 125 V DC typical | |
Display type | Monochrome graphic LCD |
Display resolution | 128 x 128 pixels |
Sampling rate | 64 samples/cycle |
Measurement current | 5…8500 mA |
Analogue input type | Voltage (impedance 5 MOhm) |
Current (impedance <= 0.3 mOhm) | |
Measurement voltage | 35…760 V AC 45…65 Hz between phases |
20…440 V AC 45…65 Hz between phase and neutral | |
Frequency measurement range | 45…65 Hz |
Number of inputs | 2 digital |
Measurement accuracy | Active energy +/- 0.5 % |
Reactive energy +/- 2 % | |
Active power +/- 0.5 % | |
Apparent power +/- 0.5 % | |
Frequency +/- 0.05 % | |
Power factor +/- 0.5 | |
Current +/- 0.5 % | |
Voltage +/- 0.5 % | |
Apparent energy +/- 0.5 % | |
Reactive power +/- 2 % | |
Accuracy class | Class 0.5S active energy conforming to IEC 62053-22 |
Number of outputs | 2 digital |
Information displayed | Tariff (4) |
Communication port protocol | Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none – 2 wires, insulation 2500 V |
JBUS | |
Communication port support | RS485 |
Data recording | Event logs |
Min/max of instantaneous values | |
Alarm logs | |
Data logs | |
Time stamping | |
Maintenance logs | |
Memory capacity | 256 kB |
Connections – terminals | Voltage circuit: screw terminal block4 |
Control circuit: screw terminal block2 | |
Current transformer: screw terminal block6 | |
Input/output circuit: screw terminal block6 | |
Relay output: screw terminal block4 | |
Ethernet network: RJ45 connector | |
mounting mode | Flush-mounted |
Mounting support | Framework |
Standards | EN 50470-3 |
IEC 62053-24 | |
IEC 60529 | |
EN 50470-1 | |
UL 61010-1 | |
IEC 62053-22:2020 | |
IEC 61557-12:2015 | |
IEC 62053-23:2020 | |
IEC 62052-11:2020 | |
IEC 62052-31:2015 | |
Product certifications | CE conforming to IEC 61010-1 |
CULus conforming to UL 61010-1 | |
Width | 96 mm |
Depth | 72 mm |
Height | 96 mm |
Net weight | 430 g |
Environment | |
Electromagnetic compatibility | Conducted and radiated emissions class A conforming to EN 55011 |
Limits for harmonic current emissions class A conforming to IEC 61000-3-2 | |
Immunity to conducted disturbances – test level: 150 kHz…80 MHz level 3 conforming to IEC 61000-4-6 | |
Voltage dips and interruptions immunity test level 4 conforming to IEC 61000-4-11 | |
Conducted RF disturbances level 3 conforming to IEC 61000-4-6 | |
Magnetic field at power frequency level 4 conforming to IEC 61000-4-8 | |
Conducted and radiated emissions class B conforming to EN 55022 | |
Limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3 | |
Electrostatic discharge – test level: 8 kV level 4 conforming to IEC 61000-4-2 | |
Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3 | |
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 | |
Surge immunity test level 4 conforming to IEC 61000-4-5 | |
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 | |
IP degree of protection | IP54 display: conforming to IEC 60529 |
IP30 rear: conforming to IEC 60529 | |
Relative humidity | 5…95 % at 50 °C non-condensing |
Pollution degree | 2 |
Ambient air temperature for operation | -25…70 °C meter |
-20…70 °C display | |
-25…-20 °C (with reduced performance) display | |
Ambient air temperature for storage | -40…85 °C |
Operating altitude | 2000 m CAT III |
3000 m CAT II | |
Packing Units | |
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 11.0 cm |
Package 1 Width | 12.6 cm |
Package 1 Length | 12.6 cm |
Package 1 Weight | 492.0 g |
Unit Type of Package 2 | S03 |
Number of Units in Package 2 | 12 |
Package 2 Height | 30.0 cm |
Package 2 Width | 30.0 cm |
Package 2 Length | 40.0 cm |
Package 2 Weight | 6.4 kg |
Unit Type of Package 3 | P12 |
Number of Units in Package 3 | 288 |
Package 3 Height | 105.0 cm |
Package 3 Width | 80.0 cm |
Package 3 Length | 120.0 cm |
Package 3 Weight | 156.0 kg |
Sale!
Power meter PowerLogic PM5310, modbus, up to 31st Harmonic, 256KB 2DI/2DO 35 alarms-Schneider Electric
Original price was: ৳ 40,100.00.৳ 32,080.00Current price is: ৳ 32,080.00.
& Delivery/Courier ChargeDocuments: Product datasheet, Instruction Sheet, CAD, Catalogue
Free Delivery on orders over ৳50,000!
- Cash on delivery
- 1-3 Days Standard Delivery Guaranteed
- No-Risk Money Back Guarantee!
- No Hassle Refunds
- Secure Payments
Only logged in customers who have purchased this product may leave a review.
Reviews
There are no reviews yet.