This digital panel meter is part of the EasyLogic Digital Panel Meter Series. This panel meter replaces multiple analog meters through single digital meter. This is a three phases ampermeter digital panel meter. It offers a direct reading with auto scaling of values, a LED indication for phase identification and a inbuild selector switch. The meter has a 4 digits, seven segments, 15 mm height and bright red LED display. Mechanical dimensions are 96 mm in width, 96 mm in height and 52 mm in depth.
Specifications | |
Main | |
Range | EasyLogic |
Product name | EasyLogic DM3000 |
Device short name | DM3110 |
Product or component type | Ammeter |
Device application | Load control |
Test laboratories | |
GenSet | |
Complementary | |
poles description | 3P + N |
3P | |
Type of measurement | Current |
[Us] rated supply voltage | 100…230 V AC +/- 20 % |
100…230 V DC +/- 20 % | |
Supply frequency | 50/60 Hz +/- 5 Hz |
Network frequency | 60 Hz |
50 Hz | |
Maximum power consumption in VA | 3 VA at 230 V AC |
Display type | LED |
Display digits | 4 |
Full scale display | 999.9 |
Control type | Selector switch built-in |
Analogue input type | Current 0…5 Athree phase |
Measurement current | 1/5 A, 50…6000 mA AC, 50/60 Hz +/- 5 Hz |
Accuracy | Current +/- 0.5 % of full scale for class 0.5 |
Device mounting | Flush |
Mounting support | Panel |
Type of installation | Indoor |
Measurement category | Category III |
Standards | IEC 61326 |
Product certifications | CE conforming to IEC 61010-1 |
Environment | |
Electromagnetic compatibility | Conducted and radiated emissions class A conforming to CISPR 11 |
Electrostatic discharge conforming to IEC 61000-4-2 | |
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 | |
Surge immunity test conforming to IEC 61000-4-5 | |
Conducted RF disturbances conforming to IEC 61000-4-6 | |
Magnetic field at power frequency conforming to IEC 61000-4-8 | |
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 | |
Harmonics conforming to IEC 61000-3-2 | |
Limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3 | |
IP degree of protection | Front panel: IP50 |
Body: IP30 | |
Relative humidity | 5…95 % |
Pollution degree | 2 |
Ambient air temperature for operation | -10…60 °C |
Ambient air temperature for storage | -25…70 °C |
Colour | Black |
Width | 96 mm |
Height | 96 mm |
Depth | 38 mm |
cut-out dimensions | 92 x 92 mm |
Net weight | 220 g |
Packing Units | |
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 9.6 cm |
Package 1 Width | 9.6 cm |
Package 1 Length | 4.35 cm |
Package 1 Weight | 304 g |
Unit Type of Package 2 | S03 |
Number of Units in Package 2 | 16 |
Package 2 Height | 30 cm |
Package 2 Width | 30 cm |
Package 2 Length | 40 cm |
Package 2 Weight | 4.9 kg |
Unit Type of Package 3 | P06 |
Number of Units in Package 3 | 128 |
Package 3 Height | 105 cm |
Package 3 Width | 60 cm |
Package 3 Length | 80 cm |
Package 3 Weight | 39 kg |