LRD01 is a TeSys LRD thermal overload relay from Schneider Electric to be used with a TeSys D contactor. It protects motors less than 0.06kW@400V thanks to a thermal range 0.10-0.16A, a tripping class 10A and phase unbalance protection. LRD01 is a TeSys LRD thermal overload relay from Schneider Electric for direct mounting on TeSys D contactors. With a thermal setting range 0.10-0.16A, a tripping class 10A and phase unbalance detection, it protects motors less than 0.06kW@400V.
It provides manual test & reset buttons, automatic reset, trip auxiliary contact and flag indicator. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Thermal overload protection relay, bimetallic type, with phase unbalance protection (differential). Direct mounting on the bottom terminals of a Tesys contactor LC1D09-D38 to form a compact starter. Light and compact, 45mm wide.
Temperature compensated for a good accuracy of the protection. Manual control with test & reset buttons, manual / automatic reset selector. Trip signaling with 1NO+1NC auxiliary contacts and trip flag indicator. Can be completed with terminal blocks for separate mounting (LAD7B, LAD96) and remote control devices (LAD703, LA7D03).
Specifications | |
Range | TeSys |
TeSys Deca | |
Product name | TeSys LRD |
TeSys Deca | |
Product or Component Type | Differential thermal overload relay |
Device short name | LRD |
relay application | Motor protection |
Product Compatibility | LC1D25 |
LC1D09 | |
LC1D12 | |
LC1D18 | |
LC1D38 | |
LC1D32 | |
Network type | DC |
AC | |
Thermal overload class | Class 10A IEC 60947-4-1 |
Thermal protection adjustment range | 0.1…0.16 A |
[Ui] rated insulation voltage | Power circuit 600 V CSA |
Power circuit 600 V UL | |
Power circuit 690 V IEC 60947-4-1 | |
Complementary | |
Network Frequency | 0…400 Hz |
Mounting support | Plate, with specific accessories |
Rail, with specific accessories | |
Under contactor | |
Tripping threshold | 1.14 +/- 0.06 Ir IEC 60947-4-1 |
Auxiliary contact composition | 1 NO + 1 NC |
[Ith] conventional free air thermal current | 5 A signalling circuit |
Permissible current | 3 A 120 V AC-15 signalling circuit |
0.22 A 125 V DC-13 signalling circuit | |
[Ue] rated operational voltage | 690 V AC 0…400 Hz power circuit IEC 60947-4-1 |
Associated fuse rating | 4 A gG for signalling circuit |
4 A BS for signalling circuit | |
[Uimp] rated impulse withstand voltage | 6 kV |
Phase failure sensitivity | Tripping current 130 % of Ir on two phase, the last one at 0 |
Control type | Red push-button stop |
Blue push-button reset | |
Temperature compensation | -4.0000000000…140.0000000000 °F (-20…60 °C) |
Connections – terminals | Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) flexible without cable end |
Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) flexible with cable end | |
Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) solid without cable end | |
Power circuit screw clamp terminals 1 0.002…0.02 in² (1.5…10 mm²) flexible without cable end | |
Power circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) flexible with cable end | |
Power circuit screw clamp terminals 1 0.002…0.009 in² (1…6 mm²) solid without cable end | |
Tightening torque | Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals |
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals | |
Height | 2.6 in (66 mm) |
Width | 1.8 in (45 mm) |
Depth | 2.8 in (70 mm) |
Net Weight | 0.273 lb(US) (0.124 kg) |
Environment | |
Climatic withstand | IACS E10 |
IP degree of protection | IP20 conforming to IEC 60529 |
Ambient air temperature for operation | -4.0000000000…140.0000000000 °F (-20…60 °C) without derating IEC 60947-4-1 |
Ambient Air Temperature for Storage | -76.0000000000…158.0000000000 °F (-60…70 °C) |
Flame retardance | V1 conforming to UL 94 |
Mechanical robustness | Vibrations6 Gn IEC 60068-2-6 |
Shocks15 Gn for 11 ms IEC 60068-2-7 | |
Dielectric strength | 1.89 kV 50 Hz IEC 60947-1 |
Standards | EN/IEC 60947-4-1 |
EN/IEC 60947-5-1 | |
UL 60947-4-1 | |
UL 60947-5-1 | |
CSA C22.2 No 60947-4-1 | |
CSA C22.2 No 60947-5-1 | |
GB/T 14048.4 | |
GB/T 14048.5 | |
EN 50495 | |
Product Certifications | IEC |
UL | |
CSA | |
CCC | |
EAC | |
BV | |
RINA | |
DNV-GL | |
LROS (Lloyds register of shipping) | |
ATEX INERIS | |
UKCA | |
Ordering and shipping details | |
Category | US10I1222347 |
Discount Schedule | 0I12 |
GTIN | 3.38911E+12 |
Returnability | Yes |
Country of origin | US |
Packing Units | |
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 1.969 in (5.000 cm) |
Package 1 Width | 3.071 in (7.800 cm) |
Package 1 Length | 3.543 in (9.000 cm) |
Package 1 Weight | 4.797 oz (136.000 g) |
Unit Type of Package 2 | S02 |
Number of Units in Package 2 | 24 |
Package 2 Height | 5.906 in (15.000 cm) |
Package 2 Width | 11.811 in (30.000 cm) |
Package 2 Length | 15.748 in (40.000 cm) |
Package 2 Weight | 7.912 lb(US) (3.589 kg) |
Unit Type of Package 3 | P06 |
Number of Units in Package 3 | 384 |
Package 3 Height | 29.528 in (75.000 cm) |
Package 3 Width | 23.622 in (60.000 cm) |
Package 3 Length | 31.496 in (80.000 cm) |
Package 3 Weight | 144.235 lb(US) (65.424 kg) |
Contractual warranty | |
Warranty | 18 months |