AX50…AX80 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC. These contactors are of the block type design with: – 3 main poles – control circuit: AC operated – add-on auxiliary contact blocks (optional) for side mounting and a wide range of accessories.
Ordering | |
Minimum Order Quantity | 1 piece |
Customs Tariff Number | 85364900 |
Popular Downloads | |
Instructions and Manuals | 9AKK107492A7059 |
CAD Dimensional Drawing | 2CDC001079B0201 |
Dimensions | |
Product Net Width | 70 mm |
Product Net Depth / Length | 110 mm |
Product Net Height | 108 mm |
Product Net Weight | 1.01 kg |
Technical | |
Number of Main Contacts NO | 3 |
Number of Main Contacts NC | 0 |
Number of Auxiliary Contacts NO | 0 |
Number of Auxiliary Contacts NC | 0 |
Rated Operational Voltage | Auxiliary Circuit 690 V |
Main Circuit 690 V | |
Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz |
Main Circuit 50 / 60 Hz | |
Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 125 A |
Rated Operational Current AC-1 (Ie) | (220 / 240 V) 55 °C 95 A |
(690 V) 40 °C 115 A | |
(690 V) 70 °C 80 A | |
Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 65 A |
(440 V) 55 °C 65 A | |
(500 V) 55 °C 55 A | |
(690 V) 55 °C 43 A | |
(380 / 400 V) 55 °C 65 A | |
(220 / 230 / 240 V) 55 °C 65 A | |
Rated Operational Power AC-3 (Pe) | (415 V) 37 kW |
(440 V) 37 kW | |
(500 V) 37 kW | |
(690 V) 37 kW | |
(380 / 400 V) 30 kW | |
(220 / 230 / 240 V) 18.5 kW | |
Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 650 A |
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 135 A | |
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A | |
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A | |
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 370 A | |
Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1300 A |
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 630 A | |
Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
(AC-3) 600 cycles per hour | |
Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V |
Rated Impulse Withstand Voltage (Uimp) | Auxiliary Circuit 6 kV |
Maximum Mechanical Switching Frequency | 3600 cycles per hour |
Rated Control Circuit Voltage (Uc) | 50 Hz 220 … 230 V |
60 Hz 230 … 240 V | |
Operate Time | Between Coil De-energization and NC Contact Closing 7 … 14 ms |
Between Coil De-energization and NO Contact Opening 4 … 11 ms | |
Between Coil Energization and NC Contact Opening 7 … 22 ms | |
Between Coil Energization and NO Contact Closing 8 … 27 ms | |
Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 | |
IP10 | |
Terminal Type | Screw Terminals |
Technical UL/CSA | |
General Use Rating UL/CSA | (600 V AC) 90 A |
Horsepower Rating UL/CSA | (120 V AC) Single Phase 5 hp |
(200 … 208 V AC) Three Phase 20 hp | |
(220 … 240 V AC) Three Phase 25 hp | |
(240 V AC) Single Phase 10 hp | |
(440 … 480 V AC) Three Phase 60 hp | |
(550 … 600 V AC) Three Phase 75 hp | |
Tightening Torque UL/CSA | Auxiliary Circuit 9 in·lb |
Control Circuit 9 in·lb | |
Main Circuit 35 in·lb | |
Environmental | |
Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 … 55 °C |
Close to Contactor without Thermal O/L Relay -40 … 70 °C | |
Close to Contactor for Storage -60 … +80 °C | |
Near Contactor for Operation in Free Air -40 … 70 °C | |
Climatic Withstand | acc. to IEC 60068-2-30 and 60068-2-11 – UTE C 63-100 specification II |
Maximum Operating Altitude Permissible | Without Derating 3000 m |
Material Compliance | |
Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
REACH Declaration | 2CMT2021-006202 |
RoHS Information | 2CMT2021-006277 |
RoHS Status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
Toxic Substances Control Act – TSCA | 2CMT2023-006525 |
WEEE B2C / B2B | Business To Business |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
Certificates and Declarations | |
CB Certificate | 9AKK107492A7074 |
CCC Certificate | 9AKK107492A7091 |
CCS Certificate | GZ23PTB00147 |
CQC Certificate | CQC2013010304646607 |
Declaration of Conformity – CCC | 2.02098E+15 |
Declaration of Conformity – CE | 1SBD250011U1000 |
UL Certificate | UL_20140702-E312527-10-7 |
Container Information | |
Package Level 1 Units | 1 piece |
Package Level 1 Width | 102 mm |
Package Level 1 Depth / Length | 143 mm |
Package Level 1 Height | 152 mm |
Package Level 1 Gross Weight | 1.12 kg |
Package Level 1 EAN | 3.47152E+12 |
Package Level 2 Units | 10 piece |
Package Level 2 Width | 240 mm |
Package Level 2 Depth / Length | 295 mm |
Package Level 2 Height | 145 mm |
Package Level 2 Gross Weight | 11.2 kg |
Classifications | |
Object Classification Code | Q |
ETIM 6 | EC000066 – Power contactor, AC switching |
ETIM 7 | EC000066 – Power contactor, AC switching |
ETIM 8 | EC000066 – Power contactor, AC switching |
eClass | V11.0 : 27371003 |
UNSPSC | 39121529 |
IDEA Granular Category Code (IGCC) | 4755 >> Contactors |
E-Number (Finland) | 3707360 |
Reviews
There are no reviews yet.