The UA75-30-00RA 220-230V 50Hz / 230-240V 60Hz is a 3-pole contactors for capacitor switching, can be used in installations in which the peak current far exceeds 100 times nominal rms current. The contactors are delivered complete with their damping resistors and must be used without additional inductances (see table below). The capacitors must be discharged (maximum residual voltage at terminals ≤ 50 V) before being re-energized when the contactors are making. Their electrical durability is 250 000 operating cycles for Ue < 500 V and 100 000 operating cycles for 500 V ≤ Ue ≤ 690 V. The UA..RA contactors are fitted with a special front mounted block, which ensures the serial insertion of 3 damping resistors into the circuit to limit the current peak on energization of the capacitor bank. Their connection also ensures capacitor precharging in order to limit the second current peak occurring upon making of the main poles. The insertion of resistors allows to damp the highest current peak of the capacitor when switching on, whatever its level. The UA..RA series 3-pole contactors are of the block type design. – Main poles: 3 main poles – Control circuit: AC operated with laminated magnet circuit – Accessories: a wide range of accessories is available.
MAIN SPECIFICATION | |
---|---|
ABB Global ID | ABB1SBL411024R8500 |
Business Area (Master Data) Name | Electrification |
Catalog Description | UA75-30-00RA 380-400V 50Hz / 400-415V 60Hz Contactor |
Division (Master Data) Name | Smart Power |
EAN | 3471522305855 |
Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 volt acc. to UL/CSA 600 volt |
SKU ID | 1SBL411024R8500 |
TECHNICAL | |
Coil Consumption | Average Holding Value 50 / 60 Hz 18 V·A Average Holding Value 50 Hz 18 V·A Average Holding Value 60 Hz 18 V·A Average Pull-in Value 50 Hz 180 V·A Average Pull-in Value 60 Hz 210 V·A |
Connecting Capacity Auxiliary Circuit | Flexible with Cable End 0.75 … 2.5 mm² Rigid Cable 1 … 4 mm² |
Connecting Capacity Main Circuit | Flexible with Cable End 6 … 10 mm² Rigid Cable 6 … 16 mm² |
Connecting Terminals (delivered In Open Position) Main Poles | M 6 (+,-) pozidriv 2 screws with 1x (13 x 10 mm) connector |
Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1300 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 630 A |
Maximum Electrical Switching Frequency | 240 cycles per hour |
Operate Time | Between Coil De-energization and NO Contact Opening 4 … 11 ms Between Coil Energization and NO Contact Closing 8 … 27 ms |
Short-Circuit Protective Devices | gG Type Fuses 200 A |
Terminal Type | Screw Terminals |
ORDERING | |
Minimum Order Quantity | 1 piece |
ENVIRONMENTAL | |
Climatic Withstand | acc. to IEC 60068-2-30 and 60068-2-11 – UTE C 63-100 specification II |
Maximum Operating Altitude Permissible | 3000 m |
RoHS Status | Following EU Directive 2011/65/EU |
CLASSIFICATIONS | |
EClass | V11.0 : 27371006 |
ETIM 4 | EC001079 – Capacitor magnet contactor |
ETIM 5 | EC001079 – Capacitor magnet contactor |
ETIM 6 | EC001079 – Capacitor contactor |
ETIM 7 | EC001079 – Capacitor contactor |
Object Classification Code | Q |
UNSPSC | 39121529 |
OTHER | |
Ambient Air Temperature | Close to Contactor for Storage -60 … +80 °C Near Contactor for Operation in Free Air (0.85 … 1.1 Uc) -40 … +55 °C Near Contactor for Operation in Free Air (Uc) -40 … +70 °C |
Degree Of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
Number Of Main Contacts NO | 3 |
Product Net Width | 70 |
Rated Control Circuit Voltage (Uc) | 50 Hz 380 … 400 V 60 Hz 400 … 415 V |
Rated Impulse Withstand Voltage (Uimp) | 8 kilovolt |
Rated Operational Power AC-6b (Pe) | (230 / 240 V) 40 °C, 50 / 60 Hz 35 kvar (230 / 240 V) 55 °C, 50 / 60 Hz 30 kvar (230 / 240 V) 70 °C, 50 / 60 Hz 25 kvar (400 / 415 V) 40 °C, 50 / 60 Hz 60 kvar (400 / 415 V) 70 °C, 50 / 60 Hz 41 kvar (400 / 415 V) 55 °C, 50 / 60 Hz 50 kvar (440 V) 40 °C, 50 / 60 Hz 65 kvar (440 V) 55 °C, 50 / 60 Hz 53 kvar (440 V) 70 °C, 50 / 60 Hz 45 kvar (500 / 550 V), 40 °C, 50 / 60 Hz 75 kvar (500 / 550 V) 55 °C, 50 / 60 Hz 65 kvar (500 / 550 V) 70 °C, 50 / 60 Hz 55 kvar (690 V) 40 °C, 50 / 60 Hz 100 kvar (690 V) 55 °C, 50 / 60 Hz 80 kvar (690 V) 70 °C, 50 / 60 Hz 70 kvar |
Rated Operational Voltage | Main Circuit 690 V |
Reviews