TeSys F contactor, 3 poles (3NO), 400A/1000V AC-3, for motor applications up to 200kW@400V. It provides a low sealed consumption 220V 40-400Hz AC coil, bolt terminals for bars or cables with lugs. For high operating rates until 2400 cycles/hour and environments until 55°C, it procures high reliability and durability. It makes installation and maintenance easy thanks to its drawer-mounted coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Specifications | |
Main | |
Range | TeSys |
Range of product | TeSys F |
product or component type | Contactor |
Device short name | LC1F |
contactor application | Motor control |
Resistive load | |
Utilisation category | AC-1 |
AC-4 | |
AC-3 | |
poles description | 3P |
[Ue] rated operational voltage | <= 1000 V AC 50/60 Hz |
<= 460 V DC | |
[Uc] control circuit voltage | 220 V AC 40…400 Hz |
[Ie] rated operational current | 500 A (at <40 °C) at <= 440 V AC AC-1 |
400 A (at <55 °C) at <= 440 V AC AC-3 | |
Complementary | |
[Uimp] rated impulse withstand voltage | 8 kV |
[Ith] conventional free air thermal current | 500 A (at 40 °C) |
Rated breaking capacity | 3200 A conforming to IEC 60947-4-1 |
[Icw] rated short-time withstand current | 3600 A 40 °C – 10 s |
2400 A 40 °C – 30 s | |
1700 A 40 °C – 1 min | |
1200 A 40 °C – 3 min | |
1000 A 40 °C – 10 min | |
Associated fuse rating | 400 A aM at <= 440 V |
500 A gG at <= 440 V | |
Average impedance | 0.26 mOhm – Ith 500 A 50 Hz |
[Ui] rated insulation voltage | 1000 V conforming to IEC 60947-4-1 |
1500 V conforming to VDE 0110 group C | |
Power dissipation per pole | 65 W AC-1 |
42 W AC-3 | |
Overvoltage category | III |
power pole contact composition | 3 NO |
Motor power kW | 75 kW at 400 V AC 50/60 Hz (AC-4) |
200 kW at 380…400 V AC 50/60 Hz (AC-3) | |
220 kW at 415 V AC 50/60 Hz (AC-3) | |
250 kW at 440 V AC 50/60 Hz (AC-3) | |
257 kW at 500 V AC 50/60 Hz (AC-3) | |
280 kW at 660…690 V AC 50/60 Hz (AC-3) | |
185 kW at 1000 V AC 50/60 Hz (AC-3) | |
110 kW at 220…230 V AC 50/60 Hz (AC-3) | |
Control circuit voltage limits | Operational: 0.85…1.1 Uc 40…400 Hz (at 55 °C) |
Drop-out: 0.3…0.5 Uc 40…400 Hz (at 55 °C) | |
Mechanical durability | 10 Mcycles |
Inrush power in VA | 1075 VA, 40…400 Hz cos phi 0.9 (at 20 °C) |
Hold-in power consumption in VA | 15 VA, 40…400 Hz cos phi 0.9 (at 20 °C) |
Maximum operating rate | 2400 cyc/h 55 °C |
Operating time | 40…65 ms closing |
100…170 ms opening | |
Connections – terminals | Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end |
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end | |
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end | |
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end | |
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end | |
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end | |
Power circuit: bar 2 cable(s) – busbar cross section: 30 x 5 mm | |
Power circuit: lugs-ring terminals 2 cable(s) 150 mm² | |
Power circuit: bolted connection | |
Tightening torque | Control circuit: 1.2 N.m |
Power circuit: 35 N.m | |
mounting support | Plate |
Heat dissipation | 14 W |
motor power range | 110…220 kW at 480…500 V 3 phases |
110…220 kW at 380…440 V 3 phases | |
110…220 kW at 200…240 V 3 phases | |
250…500 kW at 480…500 V 3 phases | |
Motor starter type | Direct on-line contactor |
Contactor coil voltage | 220 V AC standard |
Standards | IEC 60947-1 |
EN 60947-4-1 | |
EN 60947-1 | |
IEC 60947-4-1 | |
JIS C8201-4-1 | |
Product certifications | RMRoS |
CB | |
RINA | |
DNV | |
LROS (Lloyds register of shipping) | |
CSA | |
UL | |
ABS | |
BV | |
UKCA | |
Compatibility code | LC1F |
Control circuit type | AC at 40…400 Hz |
Environment | |
IP degree of protection | IP20 front face with shrouds conforming to IEC 60529 |
IP20 front face with shrouds conforming to VDE 0106 | |
Protective treatment | TH |
Ambient air temperature for operation | -5…55 °C |
ambient air temperature for storage | -60…80 °C |
Permissible ambient air temperature around the device | -40…70 °C |
Height | 206 mm |
Width | 213 mm |
Depth | 219 mm |
Operating altitude | 3000 m without derating |
net weight | 9.1 kg |
Packing Units | |
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 25.000 cm |
Package 1 Width | 25.500 cm |
Package 1 Length | 30.000 cm |
Package 1 Weight | 9.093 kg |
Unit Type of Package 2 | S04 |
Number of Units in Package 2 | 2 |
Package 2 Height | 30.000 cm |
Package 2 Width | 40.000 cm |
Package 2 Length | 60.000 cm |
Package 2 Weight | 18.836 kg |
Unit Type of Package 3 | P06 |
Number of Units in Package 3 | 10 |
Package 3 Height | 75.000 cm |
Package 3 Width | 80.000 cm |
Package 3 Length | 60.000 cm |
Package 3 Weight | 102.180 kg |
Contractual warranty | |
Warranty | 18 months |
Reviews
There are no reviews yet.